©2008 Schneider Electric. All Rights Reserved.
C-BUS NETWORK WIRING GUIDELINES
These guidelines are consistent with Best Practices and provide the best immunity
to noise.
Follow national and local electrical codes. Refer to the product’s installation •
bulletin for product-specific information on wiring, wire gauge, and so on.
In panels and enclosures, securely anchor and sleeve C-Bus network cable and •
anchor electrical power lines. This helps prevent contact between loose electrical
power conductors and the C-Bus network wiring.
Wherever possible, consolidate multiple C-Bus network Cat-5 cables outside a •
panel or enclosure so that only one C-Bus cable is brought into the enclosure.
Insulate any consolidation of multiple C-Bus network cables in panels or •
enclosures so that there are no loose wires, no exposed terminal screws, etc.
If C-Bus network cable is run in parallel with electrical power lines (outside an •
enclosure), there must be at least 6 in. (152 mm) segregation between the two
cables at all times.
If C-Bus network cable will cross an electrical power line, the crossing must be •
at a 90° angle. Also provide at least 2.5 in. (64 mm) separation between the two
cables where they cross.
Limit the current on a C-Bus network to 2 A or less.•
Limit the total length of Cat-5 cable on a single network to 3281 ft (1 km).•
MULTI-POINT SWITCHING/DIMMING/CONTROL
To control a light from two, four, or more switch locations, give the same Group •
Address to one or more buttons on each switch and the Relay or Dimmer.
To control multiple Relay or Dimmer channels from a single switch, give the •
various Relay and/or Dimmer channels the same Group Address as the switch.
OUTPUT UNIT STATUS INDICATOR ACTIVITY
For a description of the status indicators’ activity on other types of units, such as an
input unit, see the other side of this guide or the unit’s installation bulletin.
NOTE: The Unit and C-Bus indicators on output units only function when output
units are connected to 120/277 V AC.
Unit
Indicates the status of the individual unit and whether it is receiving line-level
voltage.
ON (lit): the unit is receiving line-level voltage.•
Flashing: the Local or Remote Overrides have been toggled ON or OFF.•
OFF (unlit): th• ere is no line-level voltage.
C-Bus
Indicates the status of the C-Bus network at the unit:
ON (lit): there is a C-Bus Clock and an acceptable level of C-Bus network power •
(recommended range is 22–36 V DC).
Flashing: the line voltage on the C-Bus network is marginal (15–20 V DC).•
OFF (unlit): no C-Bus System Clock or no C-Bus network power.•