6 of 12
5502DAL C-Bus DALI Gateway Installation Instructions
© 2011 Schneider Electric. All Rights Reserved.
6.0 Connection to the C-Bus Network
Installation requires connection to the unshielded twisted pair C-Bus network cable.
It is required that Category 5 data cable is used, Clipsal cat. number 5005C305B.
Two RJ45 connectors are provided for upstream and downstream network
attachment. The C-Bus network uses pink Cat.5e, polarised 15-36 Volt, twisted-pair
cable, catalogue number 5005C305B (solid) and 5005C305BST (stranded).
RJ Pin C-Bus Connection Colour
1 Remote ON Green/White
2 Remote ON Green
3 C-Bus Neg (-) Orange/White
4 C-Bus Pos (+) Blue
5 C-Bus Neg (-) Blue/White
6 C-Bus Pos (+) Orange
7 Remote OFF Brown/White
8 Remote OFF Brown
Table 1. C-Bus network wiring colour codes
Figure 1. RJ45 pin assignments for plugs and sockets