5502DAL C-Bus DALI Gateway Installation Instructions
© 2011 Schneider Electric. All Rights Reserved.
7.0 Network Burden
The DALI Gateway product incorporates a software selectable network burden.
The network burden can be enabled using the C-Bus Installation Software.
A network burden may or may not be required to ensure correct operation of
the C-Bus network. If in doubt, consult the C-Bus calculator (Network Design
Verification Software Utility) before proceeding with the hardware installation.
The graphical user interface (GUI) software is designed to prevent the burden from
accidental selection.
8.0 C-Bus Side Programming Requirements
The DALI Gateway product incorporates a C-Bus PC interface module for
communications to the C-Bus network. Programming of the C-Bus side of the
network interface can be done in the same manner as programming a standard
PC interface.
The DALI Gateway must be programmed to set a unique identification (unit address)
and mode of operation on the C-Bus network. The C-Bus Installation Software can
be used to configure all operational parameters.
The DALI Gateway is programmed using C-Bus Toolkit Software.
The C-Bus Toolkit is available for download from the Clipsal website
(www.clipsal.com/cis).
9.0 Power Surges and Short Circuit Conditions
The 5502DAL C-Bus DALI Gateway is not directly connected to the mains. Each
unit incorporates transient protection circuitry, but additional external power surge
protection devices should be used to enhance system immunity to power surges. It
is strongly recommended that over-voltage equipment, such as the Clipsal 970, be
installed at the switchboard.
10.0 Megger Testing
Megger testing must never be performed on the C-Bus data cabling or terminals as
it may degrade the performance of the network.
Megger testing the mains wiring of an electrical installation that has C-Bus units
connected will not cause any damage to C-Bus units. Since C-Bus units contain
electronic components, the installer should interpret megger readings with due
regard to the nature of the circuit connection.
11.0 Important Warning
The use of any non C-Bus software in conjunction with the hardware installation,
without the consent of Clipsal, may void any warranties applicable to the hardware.