C-BUS TRAINING MANUAL - VOL 1
34
IMPORTANT Using the above pairing ensures a mutual twist between conductors and C
Bus terminals, providing increased immunity to electromagnetic interference.
It is recommended that the C-Bus cable be terminated by twisting the pair together or by using a
bootlace crimp as shown in Figure 1.
Figure 1 – Terminating with a bootlace crimp
When terminating the C-Bus cable, do not solder as in Figure 2. This may cause “cold flow”.
Figure 2 – Soldering may cause cold flow
When twisting the pair together, avoid frayed terminations as shown in Figure 3.
Figure 3 – Avoid frayed terminations
The Clipsal C-Bus data cable is strongly recommended due to its distinctive pink outer sheathing.
This reduces confusion between a C-Bus network and information systems (such as data, fire and
telephone), at the same installation. The Cat-5 UTP also has a 240 V mains rated outer sheath. This
is a requirement where the cable enters a switchboard, and is present in the same enclosure as single
insulated mains wire.
The C-Bus connectors are wired as a standard patch lead, as shown in Table 1