1.3 Mains Segregation
With all C-Bus units that have mains as well as 36Vd.c. bus connections, care must be taken to
adequately separate the 240Va.c. wiring from the bus wiring. Pink C-Bus Cat-5 UTP, with its mains
rated outer sheath, must be used within the confines of a switchboard.
Wiring practices vary from installer to installer. Sometimes the mains cable entering the switchboard
is double insulated, while other times it is single insulated. When it is double insulated, the outer
insulation must be stripped back to allow the connection of mains wires to the DIN unit power supply
and output terminals.
No isolation issues can be expected between C-Bus and a single insulated mains cable, when the
pink C-Bus Cat-5 cable enters a switchboard and plugs straight into a DIN module.
The 300 mm pink Cat-5 patch leads supplied with all DIN units are used to loop in and out of any
other DIN units within the enclosure.
Where more than one pink Cat-5 cable enters the switchboard, care must be taken to ensure that any
join made between multiple Cat-5 cables, is effectively insulated with no exposed terminal screws etc.
Consider terminating multiple C-Bus Cat-5 cables outside the switchboard, and bringing just one into
the RJ socket on a DIN unit.
The mains rated pink sheath allows the C-Bus Cat-5 cable to run closer to mains wiring than would
otherwise be allowed. To give the greatest margin of noise immunity within the switchboard and
overall installation:
• always maintain 150 mm of separation between C-Bus and mains cable, when running C-Bus
cable in parallel with mains
• ensure that C-Bus always crosses mains cable at a 90 degree angle, with at least 60 mm of
separation.
Most importantly, securely anchor both Cat-5 and mains cable in switchboards. This provides
an additional safety margin against contact between loose mains conductors, and the C-Bus
36Vd.c. wiring.
IMPORTANT These issues are covered by wiring regulations. An installer must ensure that
wiring is carried out in a safe manner. The safety and protection of users of
equipment is of the highest importance. The product warranty will be affected if
a failure is found to be caused by poor wiring practice. In addition, the isolation
between mains and C-Bus wiring is one of the key checks made during a CIS
Approved Installer visit.