1250SM0904R10/09 C-Bus™ Basic Programming
10/2009 C-Bus™ Products Training Course
© 2009 Schneider Electric. All Rights Reserved. 103
Figure 85 - The logic tab of a dimmer
Below is an example of a simple MIN Logic Condition. You will see that
there are 3 parts to programming the logic condition:
selecting the dimmer channels that you want to operate with logic.
selecting a logic group from the drop down box.
selecting the logic operator (MIN logic) to link the selected dimmer
channel’s group address and the logic group.
Figure 86 - Dimmer using MIN logic
When using minimum logic on a dimmer, the output of the selected
channels are capped at the level of the logic group address. The load output
will always reflect the minimum level between the group address and logic
group address levels.
The images below show the relationships between the level of the:
group address
logic group
load on the dimmer channel.