Clipsal C-Bus Manual de Instruções Página 113

  • Descarregar
  • Adicionar aos meus manuais
  • Imprimir
  • Página
    / 148
  • Índice
  • MARCADORES
  • Avaliado. / 5. Com base em avaliações de clientes
Vista de página 112
1250SM0904R10/09 C-Bus™ Basic Programming
10/2009 C-Bus™ Products Training Course
© 2009 Schneider Electric. All Rights Reserved. 107
Recovery Tab
The Recovery tab affects the behaviour of each dimmer channel on power
up.
If the C-Bus dimmer loses it mains power, the unit will shut down. When
mains power is restored to the C-Bus dimmer, the channels will (by default)
restore to the previously known levels after the specified delay period
(default 5 seconds).
By removing the tick from a relay channel’s check box, the following
behaviours may be programmed into each individual channel, after mains
power is restored:
turn ON (100%)
turn OFF (0%)
set level using the slider (1% to 99%).
Figure 92 - The Recovery tab of a dimmer
Global Tab
The Global tab allows various parameters to be configured for the entire
relay unit.
Figure 93 - The Global tab of a dimmer
Vista de página 112
1 2 ... 108 109 110 111 112 113 114 115 116 117 118 ... 147 148

Comentários a estes Manuais

Sem comentários