1.0 Basic Learn Mode
The C-Bus
®
2 system features a mode, called Learn Mode, which allows Units on a C Bus Network
to listen to each other and learn what they need to do by simple button presses on the Units.
To identify which are capable of entering Learn Mode check:
• Any label indicating C-Bus2
• Purple coloured case on output units.
• Orange LED’s on the input units.
The source of this new functionality is the ability to assign a load, such as a light, with a controller,
such as a key input unit, by touching the two units one after the other. This is done while in a mode
called “Learn Mode”, so named because the C Bus Network can now learn what the user wants
to do.
NOTE: For safety reasons Learn Mode can be disabled from the C-Bus Installation
Software to protect the programming of the Network.
1.0.1 Entering and Exiting Learn Mode
1. Find any Learn Mode output unit.
2. Press and hold down any of the Quick Toggle buttons on any output units for 10 seconds. The
Unit and C-Bus LED’s will then begin to ash alternately.
The “Unit” and “C-Bus
®
” indicators may initially flash together for up to 20 seconds before
flashing alternately. Various Network parameters are initialised during this.
3. On any of the output units, press and hold down any of the Quick Toggle buttons for 2 seconds.
4. The Unit and C-Bus LED should now be on solid.
The C-Bus clock will then have been successfully enabled on that particular output unit. If Learn Mode
has not been exited successfully within 10 minutes, all Units will resume normal operation without
storing any changes.
1.0.2 Selecting Output Channels
While in Learn Mode the Local Toggle buttons on Output Units can be pressed. The load will be
switched on and the appropriate indicator will light up on the Output Unit. Multiple loads may be
selected, across multiple Output Units. A mix of different Output Types (Dimmer and Relay) can also
be selected if required.
1.0.3 Select the Output Channels required for operation.
Any previously programmed associations between Input and Output Units can be overwritten by
a Learn operation. To ensure this doesn’t happen, the programmer should only use each Output
channel and each Input switch only ONCE when using Learn Mode.