2B. Basic Programming
the key. If the key is released before the rst double ash, a 5 second timer will be set. This can be
useful for testing purposes.
When a timer function has been selected the LED will give a single ash at 1 second intervals to
ensure the user is aware of this function being selected for that key.
1.2 Super Learn Mode
Super Learn Mode is a powerful utility, allowing the user to:
• Reset Group Addresses on an Output Unit to $FF Unused
• Reset Area Addresses on an Output Unit to $FF Unused
• View the status of the Network Burden on an Output Unit
• Manually Enable or Disable the Network Burden on an Output Unit
1.2.1 Entering Super Learn Mode
A C-Bus2 Learn capable Output Unit is placed in Super Learn Mode by double clicking an Local
Toggle button whilst that Unit is in Learn Mode.
All loads and associated indicators on that Unit will come on, and the “Unit” indicator will ash rapidly.
The “C-Bus” indicator then shows the state of the Burden for that Unit. If the “C-Bus” indicator is on,
then the Burden is enabled, if the “C-Bus” indicator is off, then the Burden is disabled.
1.2.2 Resetting To Defaults
Super Learn Mode may be used to clear Group Addresses from Output Units and restore other
factory default settings. Upon exiting Super Learn Mode, all Group Addresses for the selected
channels will be reset (cleared to $FF ‘Unused’).
When a Unit is placed in Super Learn Mode all channels on that Unit are selected by default, however
individual channels may be de-selected as required. Only the selected channels will be cleared.
• If ALL channels on a C-Bus2 Output Unit are selected, then the Area Address and various
other factory settings will be reset. If all channels on a Unit are not selected, the Area Address
of that Unit will remain unchanged.
• Channels on all other output units may be selected (even though they are not in Super Learn